Microtel Series 1000EX User Manual

Page 38

Advertising
background image

MICROTEL Series 1000EX Dialer

32

Configuring Input/Output Modules

The Series 1000EX features true modularity--I/O channels operate completely
independently of each other. Using the following commands, each I/O channel in your
dialer can be configured to operate uniquely to satisfy your application requirements. For
each I/O channel, you may record a voice message, choose the format of spoken status
reports, program an alarm integration delay, alarm call out operation, and telephone
number calling sequence. Analog inputs also have user-selectable low and high alarm
setpoints.

NOTE: Always verify the I/O channel TYPE before proceeding to configure any other

values for a channel. The dialer will reset a channel’s settings when this
channel’s TYPE is modified. If you are adding a new I/O channel to your
dialer, you must configure this channel’s TYPE first. Refer to Advanced Topics
for information on adding I/O modules to an existing configuration.


NOTE: Input modules come from the factory configured as STATUS only. At the very

least, you must configure your inputs to Call On Alarm (described below).


The following commands configure and report the current values for the channel level
operations of the Series 1000EX. They are in the order presented in the text. These
settings include:

Section Current

Setting

Change Setting Meaning

Channel Type

*cc2* **cc2nn*

I/O Type of channel cc

Alarm
Configuration

*cc8* **cc8n*

Determines how channel cc’s alarm operation
will be handled

Report Status
Flag

*cc7* **cc7n*

Tells the dialer to report channel cc’s status as
part of its answer message (n=0:Don’t, 1:Do)

Channel
Telephone List

*cc4* **cc41t*

List of telephone numbers that will be called to
report an alarm condition for channel cc

Channel Status

*cc0*

Reads back the current status for channel cc

Clear Channel
Counters

**cc0* Clears the Counter, Runtime, Time In Alarm

values for the channel cc

Channel Voice
Name

*cc1* **cc1*~

Spoken name for channel cc

Channel
Report Format

*cc3* **cc3nn*

Selection of status information that is spoken
for channel cc

Channel
ON/OFF Delay

*cc5* **cc5nMMSS*

Time that a physical state change must be
maintained until channel cc’s alarm state
changes

Analog High
Setpoint

*cc90* **cc90aaa*

High setpoint for an analog input (in percent).
Used for analog alarm monitoring

Analog Low
Setpoint

*cc91* **cc91aaa*

Low setpoint for an analog input (in percent).
Used for analog alarm monitoring

Advertising