5.2. Emergency Broadcast by Emergency Telephone or Fire Button

*1

Even when another emergency telephone or fire button operates after Warning Announcement is made,
Evacuation Announcement informs the first-operated device's floor as the fire floor.

*2

After All-zone Broadcast Interval Timer's set time is up, only all-zone broadcast can be made. Broadcasting
floors cannot be changed, nor can broadcast be reset.

Activation from the emergency telephone or fire button
(Current general-purpose broadcast stops.)

Fire indicator lights.

Fire floor indicator lights.

Zone indicators of the fire floor and interlock
floor light. (Interlock mode)

Zone indicators of all floors light. (All-zone
interlock mode)

Warning Mode

Evacuation mode

Warning Announcement (

and

)

Broadcasting floor: Fire floor and interlock floor (Interlock
mode) or all floors (All-zone interlock mode)

Information on the floor first alarm activating is included.

M5

M1

All-zone Broadcast
Interval timer [Off]

All-zone Broadcast
Interval timer [0 minute]

Time setting for All-zone
Broadcast Interval timer

All-zone Broadcast Timer starts.

Evacuation Announcement (

)

*1

Broadcasting floor: Fire floor and interlock floor
(Interlock mode) or all floors (All-zone interlock mode)
Information on the floor first alarm activating is included.

M2

All-zone Evacuation Announcement (

)

*1,*2

Broadcasting floor: All floors
Information on the floor first alarm activating is included.

M2

Time is up.

Evacuation Announcement (

)

*1

Broadcasting floor: Fire floor and interlock floor
(Interlock mode) or all floors (All-zone interlock mode)
Information on the floor first alarm activating is included.

M2

Using the PA microphone

, make appropriate announcements

for evacuation. After the microphone announcement is completed,
only the "Second signal" warning tone is repeated.

Select other floors as well as required.

*2

1

Fire

False Alarm Announcement

• Key numbers are those shown in "4.

NOMENCLATURE AND FUNCTIONS" on
p. 7.

• Marks

,

....in this section represent

voice alarms or voice operation guides. (p. 17)

• Marks

,

....represent the indications to

be displayed on the screen. (p. 18)

M2

M1