The microphone is given the highest priority and can be used at any time of these procedures. The
following message is displayed during the microphone announcement.

Represents one of the three voice alarm messages, Warning, Evacuation or False Alarm.

Warning Announcement

Repeats twice a combined broadcast of the first signal +
announcement by female voice, "Attention please. The fire alarm
system (on the [nth] floor) is indicating a fire. We're investigating the
cause. Please wait for further information."

Evacuation Announcement

Continuously repeats a combined broadcast of the first signal +
announcement by male voice, " There is a fire [on the [nth] floor].
Please evacuate as quickly as possibie." + first signal + same
announcement + second signal. If an announcement is made using
the PA microphone during the Evacuation Announcement, only a
second signal tone is repeatedly sounded after microphone
announcement completion.

False Alarm Announcement

Repeats twice a combined broadcast of the first signal +
announcement by female voice, "Attention please. A few minutes ago
we announced there may be a fire. However, there is no fire. Once
again, there is no fire."

M3

M2

M1

Press the broadcast floor selector.

Transmitted a warning announcement. Visit and check the site. Press the evacuation
announcement key when there is a fire. If there is no fire, press the false alarm key.

Received a fire signal. Visit and check the site. Press the evacuation announcement key when there
is a fire. If there is no fire, stop the automatic fire alarm system, then press the emergency reset
key.

M6

M5

M4

5.4. Voice Message Table

5.4.1. Voice alarm message
The following messages are provided from the speakers on the broadcasting floor.

Floor information in Warning/Evacuation Announcement

(1) Manually-operated emergency announcements contain no fire floor information.
(2) Even when another fire detector operates after Warning Announcement is made, the first-operated

detector's floor is used in Evacuation Announcement.

5.4.2. Voice operation guide
The following messages are provided only from the monitor speaker on the front operation section.