Toa RM-971 User Manual

Page 16

Advertising
background image

16

False Alarm Announcement

Press the False Alarm Announce-
ment key

.

9

False Alarm Announcement (

)

Broadcasting floor: Floors to which Warning Announcement or Evacuation

Announcement was made

M3

Reset the fire detector, emergency
telephone or fire button.

Extinguishment of a fire

Press the Emergency reset key

.

2

• Fire indicator is extinguished.
• Fire floor indicator is extinguished.
• Zone indicator is extinguished.

Restoration

Broadcast mode the system was last in before
Warning Announcement was made is restored.

If the Emergency reset key is pressed
without resetting the fire detector,
emergency telephone or fire button, the
system interprets the key depression as
fire status and initiates broadcast.

When a false alarm or the extinguishment
of a fire is confirmed, be sure to reset the
fire detector, emergency telephone or fire
button before pressing the Emergency
reset key.

EVACUATION

FALSE

ALARM

B

Continued from previous page

A

Continued from previous page

*1

If one of these devices is operated in the middle of Warning Announcement, Evacuation Announcement is
made after the Warning Announcement message is completed.

*2

When the broadcasting floor is selected manually, announcements are not broadcast to the floor next
above the selected floor.

*3

When a fire detector, emergency telephone or fire button operates after manually-operated Warning
Announcement is completed, subsequent Evacuation Announcement contains floor information.

*4

During the operation of Evacuation Announcement Interval Timer, even when the Broadcast reset key

is

pressed and broadcast is reset, the Evacuation timer continues to operate without stopping.

*5

After All-zone Broadcast Interval Timer's set time is up, only all-zone broadcast can be made. Broadcasting
floors cannot be changed, nor can broadcast be reset.

11

The PA microphone can be used at any time because it is given the highest priority.

If the CPU failure indicator lights or flashes during the operation of the system, open the door and set the
computer control on-off switch to the OFF position. This permits attenuator-free all-zone broadcast to be
made using the PA microphone. (See p. 24.)

Advertising