For two pipe installation, Vent and combustion air piping, Single pipe (n9mp1 models) – Sears 9MPD125L20B1 User Manual

Page 10: Direct vent (n9mp2 models), Dual certified f9mpd models), Vent & combustion air piping, Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each

appliance connected to the venting system being
placed into operation, could result in carbon
monoxide poisoning or death:

The following steps shall be followed for each
appliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and horizontal

pitch, as required in the

National Fuel Gas Coder ANSI

Z223.1/NFPA 54

or

CSA B 149.1, Natural Gas and

Propane Installation

Code and these instructions. Deter­

mine that there is no blockage or restriction, leakage,

corrosion and other deficiencies which could cause an

unsafe condition.

3. As far as practical, close all building doors and windows

and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected

to the venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they are

operating at maximum speed. Do not operate a summer
exhaust fan.

6

. Followthe lighting instructions. Place the appliance being

inspected into operation. Adjust the thermostat so

appliance is operating continuously.

7. Test for spillage from draft hood equipped appliances at

the draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle. (Figure

6

)

8

. If improper venting is observed, during any of the above

tests, the venting system must be corrected in
accordance with the

National Fuel Gas Code, ANSI

Z223.1/NFPA 54

and/or

CSA B149.1, Natural Gas and

Propane Installation Code.

9. After it has been determined that each appliance

connected to the venting system properly vents when
tested as outlined above, return doors, windows, exhaust
fans, fireplace dampers and any other gas-fired burning
appliance to their previous conditions of use.

For Two Pipe Installation

This furnace can NOT be common vented or connected to any
type B, BW or Event or vent connector, nor to any portionof a facto­
ry-built or masonry chimney. If this furnace is replacing a previous­
ly common-vented furnace, it may be necessary to resize the
existing vent and chimney to prevent oversizing problems for the
other remaining appliance(s). See

"Venting and Combustion Air

Check"\n

this section. This furnace MUST be vented to the out­

side.

4. Vent and Combustion Air Piping

WARNING

CARBON MONOXIDE POISONING HAZARD.

Failure to properly vent this furnace could result in
death and/or personal injury.

Use methods described here to provide combustion
and ventilation air.

Single Pipe (N9MP1 Models)

This furnace is certified as a category IV appliance. This furnace
requires ventilation openings to provide air for proper combustion
and ventilation of flue gases. All duct or openings for supplying

combustion and ventilation air must comply with the gas codes or
in absence of local codes, the applicable national codes.

When the installation is complete, see the "

Venting and Combus­

tion Air Check'

in this manual.

Direct Vent (N9MP2 Models)

This furnace is certified as a category IV appliance. This furnace
uses outside air for combustion ONLY, it MUST be taken from the
same atmospheric pressure zone as the vent pipe. See

Confined

Space Installation

in the

Combustion and Ventilation Air

in this

manual.

Dual Certified f9MPD Models)

This furnace is certified as a category IV appliance. This furnace
can be installed as a direct vent furnace using outside air for com­

440

01 1020 04