Figure 7 direct vent termination clearance – Sears 9MPD125L20B1 User Manual

Page 13

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Figure 7

Direct Vent Termination Clearance

65-2

AREA WHERE TERMINAL IS NOT PERMITED

Item

Clearance Description

Canadian Installation (1)

U.S. Installation (2)

A

Clearance above grade, veranda, porch, deck, balcony, or
anticipated snow level

12" (30cm)#

12" (30 cm)

В

Clearance to a window or door that may be opened

6" (15 cm) for appliances s 10,000 BTUH (3kW), 12" (30
cm) for appliances > 10,000 ßfuh (3 kW) and < 100,000 Btuh
(30 kW), 36" (91 cm) for appliances > 100,000 Btuh (30 kW)

6" (15 cm) for appliances s 10,000 BTUH (3kW), 9" (23 cm)

for appliances > 10,000 Btuh (3 kW) and < 50,000 Btuh (15

kW), 12" (30 cm) for appliances > 50,000 Btuh (15 kW)

C

Clearance to a permanently closed window

*

*

D

Vertical clearance to a ventilated soffit located above the
terminal within a horizontal distance of 2' (61cm) from the
centerline of the terminal

E

Clearance to an unventilated soffit

*

*

F

Clearance to an outside corner

*

G

Clearance to an inside corner

*

*

H

Clearance to each side of the centerline extended above
electrical meter or gas service regulator assembly

3' (91 cm) within 15' (4.5 m) above the meter/regulator
assembly

3' (91 cm) within 15' (4,5 m) above the meter/regulator
assembly

1

Clearance to service regulator vent outlet

3’ (91 cm)

*

J

Clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance

6" (15 cm) for appliances £ 10,000 BTUH (3kW), 9" (23cm)
for appliances > 10,000 Btuh (3 kW) and < 100,000 Btuh (30
kW) and < 50,000 Btuh (15 kW), 12” (30 cm) for appliances
>50,000 Btuh (15kW)

6" (15 cm) for appliances s 10,000 BTUH (3kW), 9" (23cm)

for appliances > 10,000 Btuh (3 kW) and < 50,000 Btuh (15

kW), 12" (30 cm) for appliances > 50,000 Btuh (15 kW)

К

Clearance to a mechanical air supply inlet

6' (1.83 m)

3' (91 cm) above if within 10' (3m horizontally)

L

Clearance under a veranda, porch, deck, or balcony

12" (30 cm)t

*

М

Clearance to each side of the centerline extended above or
below vent terminal of the furnace to a dryer or water heater
vent, or other appliance's direct vent intake or exhaust.

12" (30 cm)

12" (30 cm)

N

Clearance from a plumbing vent stack

3' (91 cm)

3' (91 cm)

(1,) In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

(2.) In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

#

18" {46 cm) above roof surface

+ Permitted only if veranda, porch, deck, or balcony Is fully open on a minimum of two sides beneath the floor,

*

For clearances not specified in ANSI Z223,1/NFPA 54 or CSA Bl 49.1, clearances shall be in accordance with local installation codes and the requirements of the gas supplier and the manufacture's installatioi

instructions.

Notes:

1. The vent for this appliance shall not terminate

a, Over public walkways; or
b, Near soffit vents or crawl space vents or other areas where condensate or vapor could create a nusiance or hazard or property damage: or
c, Where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other equipment.

2. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the combustiob products of adjacent vents,

Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.