Honeywell sv9541m "smart valve" trouble shooting, 144 i – Sears 9MPD125L20B1 User Manual

Page 44

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

The

6

+ X designation indicates a combination of flash codes:

6

flashes shows the control is in soft lockout, followed by X flashes to indicate

the reason the control went into soft lockout. Last status code indicates repair to address first

HONEYWELL SV9541M "SMART VALVE" Trouble shooting

LED

STATUS

INDICATES

CHECK/REPAIR

Off

No power to system control.

Line voltage input at LI and Neutral connectors on ST9160B Fan Timer.

Low voltage (24V) power at 24 VAC and COM terminals on ST9160B

System wiring harness is in good condition and securely connected.

Heartbeat

Bright - Dim

Normal indication whenever the system is powered, unless some

abnormal event has occurred.

Not Applicable - Normal Operation (stand by or call for heat)

2 Flashes

Pressure switches closed when it should be open

(I.e. when call for heat begins).

(Combustion blower is not energized until pressure switches

opens)

Pressure switches stuck closed (system will wait for pressure switch to

open).

Pressure switches miswired or jumpered.

3 Flashes

Pressure switches, open when they should be closed (i.e. longer

than 30 seconds after combustion blower/inducer is energized).

System goes into 5-minute delay period, with combustion blower/

inducer off. Atendofthe 5-minute delay, another cycle will begin.

Ignition system control switch must be in the ON position.

Pressure switches operation, tubing, and wiring.

Restrictions in furnace air intake or vent piping.

4 Flashes

Main Limit or Roll Out Switch is open.

Combustion blower is energized. Circulating blower is energized

heat speed.

Main limit switch.

Manual reset burner rollout switch.

Limit and rollout switch wiring is in good condition and securely

connected.

5 Flashes

Flame signal sensed out of proper sequence.

Combustion blower is energized. Circulating blower is energized

heat speed after the "ON" delay.

Flame at pilot burner.

6 Flashes +

1 Flash

Soft Lockout.

Failed to light pilot during 90 sec. trial for ignition

Combustion air blower is de-energized. Circulating blower is de­

energized after the "OFF" delay.

After 5-minute delay time, control system will reset and initiate a

new ignition sequence.

Gas supply off or pressure too low or high for appliance to operate.

Damaged or broken HSI element

Line voltage HOT lead wire not connected to LI terminal on ST91 GOB.

Furnace not properly earth grounded.

Flame sense rod contaminated or In incorrect position.

Pilot burner located In incorrect position.

Pilot burner lead wires are in good condition and popery connected.

Pressure switches operation, tubing, and wiring.

6 Flashes +

2 Flashes

Soft Lockout.

Last failure was Flame Sense lost during run.

Maximum recycle count exceeded

Combustion air blower is de-energized. Circulating blower is

de-energized alter the "OFF" delay.

After 5-minute delay time, control system will reset and initiate a

new ignition sequence.

Gas supply off or pressure too low or high for appliance to operate.

Line voltage HOT lead wire not connected to LI terminal on ST91 GOB.

Furnace not properly earth grounded.

Flame sense rod contaminated or in incorrect position.

Pilot burner located in incorrect position.

Pilot burner lead wires are in good condition and properly connected.

Cycling, pressure switch

Condensate drain blocked

Pressure switches operation, tubing, and wiring.

144 I