Additional lp connection requirements, Final check, Electrical wiring – Sears 9MPD125L20B1 User Manual

Page 33: Power supply wiring, J-box relocation, Thermostat, Optional equipment, Humidifier/electronic air cleaner, Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

NOTE: Refer to Figure 30 or Figure 31 for the general layout at

the furnace. The rules listed apply to natural and LP gas pipe
installations.

NOTE: On the Dual Certified or Direct Vent models, install the gas
pipe grommet to the furnace side panel with the gas pipe entry. If
needed, remove the

2"

hole plug and relocate to the open hole in

the furnace side panel.

^ WARNING

FIRE OR EXPLOSION HAZARD

Failure to properly install metal gas connector

could result in death, bodily injury and/or property
damage.

A flexible corrugated metal gas connector must be
properly installed, shall not extend through the side
of the furnace,and shall not be used inside the
furnace.

Black iron pipe shall be installed at the furnace gas

control valve and extend a minimum of 2" outside
furnace casing.

4.

Use black iron or steel pipe and fittings or other pipe ap­

proved by local code.

NOTE: The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.

5.

Use groundjoint unions and install a drip leg no less than 3 "

long to trap dirt and moisture before it can enter gas valve.

6.

Use two pipe wrenches when making connections to pre­

vent gas valve from turning.

7.

Install a manual shut-off valve external to furnace casing

and tighten all joints securely.

Additional LP Connection Requirements

1.

Have a licensed LP gas dealer make all connections at stor­

age tank and check all connections from tank to furnace.

2.

If copper tubing is used, it MUST comply with limitation set in
National Fuel Gas Code or CGA codes.

3.

Two-stage regulation of LP gas is recommended.

Final Check

1. The furnace and the gas valve must be disconnected from the

gas supply piping system during any pressure testing of that
system at test pressures in excess of Vz " PSIG. Close the
manual shut-off valve before testing at such pressures.

2. When installation is complete, test all pipe connections for

leaks with the gas pressure less than Vz" PSIG to the gas

valve.

3.

Apply a commercial soap solution to all Joints to test for

leaks. Correct any leaks indicated by bubbles.

4.

Correct even the smallest leak at once.

5.

Check for leaks at gas valve and orifice connections to the

burner manifold along with the pilot tube connections to the

valve and pilot assembly while the furnace is operating.

6. Electrical Wiring

WARNING

ELECTRICAL SHOCK HAZARD.

Failure to do so could result in death, personal
injury and/or property damage.

Turn OFF electrical power at fuse box or service

panel before making any electrical connections
and ensure a proper ground connection is made
before connecting line voltage.

Power Supply Wiring

The furnace MUST be electrically wired and grounded in accor­
dance with local codes, or in the absence of local codes with the
latest edition of The National Electric Code, ANSI NFPA 70 and/or
The Canadian Electric Code CSA C22.1.

The power supply to the furnace connections must be between
104 VAC and 127 VAC during furnace operation for acceptable
performance.

Field wiring connections must be made inside the furnace connec­

tion box. A suitable strain relief should be used at the point the
wires exit the furnace casing.

Copper conductors shall be used. Line voltage wires should
conform to temperature limitation of 63° F (35° C) rise and be sized
for the unit maximum amps stated on the rating plate. Add the full
load amps for potential field-installed accessories such as elec­
tronic air cleaners and humidifiers thaf would receive power from
the furnace control. The furnace control is rated for a maximum of
0.8 amps combined for EAC and Hum. Consult NECor local codes
for proper wire and circuit sizing.

J-Box Relocation

TheJ-box is installed on left side of casing. An alternate J-box
location on right side can be used.

1.

Remove bag containing two hole plugs and two self tapping

screws from loose parts bag in blower compartment.

2.

Remove two screws holdingj-box to casing.

3.

Move large hole plug from right to leftj-box location.

4.

Move J-box to alternate location and attach using two self

tapping screws from bag.

5.

Apply two hole plugs from bag at leftJ-box location.

Thermostat

Thermostat location has an important effect on the operation of the
unit. Eollow instructions included with thermostat for correct
mounting and wiring.

Low voltage connections to furnace must be made on terminal
board to fan control.

Set thermostat heat anticipator in accordance with the

Technical

Support Manual.

Optional Equipment

All wiring from furnace to optional equipment MUST conform to lo­
cal codes or, in the absence of local codes with the latest edition of
The National Electric Code, ANSI NFPA 70 and/or The Canadian

Electric Code CSA C22.1. Install wiring in accordance with
manufacturer's instructions. The wiring MUST have a minimum

temperature rating of 105° C.

Humidifier/Electronic Air Cleaner

The furnace is wired for humidifier and/or electronic air cleaner
connection.

440

01 1020 04

[33]

Advertising