Horizontal termination, Using exterior risers, Vertical termination – Sears 9MPD125L20B1 User Manual

Page 27: Vent termination shielding

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Install all couplings, nipples and elbows using proper proce­

dures for Joining Pipe and Fittings and maintain spacing
between vent and combustion air piping as indicated in

Figure 20 through Figure 28 .

Horizontal Termination

1.

Cut two holes. 2 V

2

" for 2" pipe, 3" for 2 V

2

" pipe, or 3 V

2

" for

3 " pipe. Do NOT make the holes oversized, or it will be nec­
essary to add a sheet metal or plywood plate on the outside

with the correct size hole in it.

2.

Check hole sizes by making sure it is smaller than the cou­

plings or elbows that will be installed on the outside. The
couplings or elbows MUST prevent the pipe from being
pushed back through the wall.

3.

Extend vent pipe and combustion air pipe through the wall

^/4

" to T" and seal area between pipe and wall.

4.

Install the couplings, nipple and termination elbows as

shown and maintain spacing between vent and combustion
air piping as indicated in Figure 20 and Figure 21.

A metal shield is recommended 18" x 18 " min. or 18" min. diameter
around the venttermination at the exterior wall to protect the house
exterior materials from flue product or condensation (freezing)
damage.

Using Exterior Risers

1

.

Install elbows and pipe to form riser as shown in Figure 21.

2.

Secure vent pipe to wall with galvanized strap or other rust

resistant material to restrain pipe from moving.

3.

Insulate pipe with Armaflex or equivalent moisture resistant

closed cell foam Insulation or Fiberglass insulation if boxed
in and sealed against moisture.

Vertical Termination

1

.

Figure 22 shows the proper installation and clearances for

vertical vent termination. The vertical roof termination

should be sealed with a plumbing roof boot or equivalent
flashing. The inlet of the intake pipe and end of the exhaust

vent must be terminated no less than

12

" above the roof or

snow accumulation level, and

12

' away from a vertical wall

or other protrusion.

2.

If the vent system is installed in an existing chimney make

sure clearances shown in Figure 22 are maintained. Flori-
zontal section before the termination elbow can be ex­

tended on the inlet air to provide necessary clearance.

Vent Termination Shielding

Under certain wind conditions some building materials may be af­

fected by flue products expelled in close proximity to unprotected
surfaces. Sealing or shielding of the exposed surfaces with a cor­
rosion resistant material (such as aluminum sheeting) may be re­
quired to prevent staining or deterioration. The protective material
should be attached and sealed (if necessary) to the building before
attaching the vent terminal.