H T C D C C o n t r o l A l a r m s

P

ASSIVE

A

LARMS

Passive alarms flash the alarm code and display process temperature until the
alarm condition goes away, or it becomes a shutdown alarm.

C o d e

D e s c r i p t i o n

A l a r m L E D

P1

Process Temperature Deviation

Blinking Red

S

H U T D O W N

A

L A R M S

Shutdown alarms flash the alarm code and display process temperature. The HTC
process air heater should stop when the process temperature is below 150°F
(65.6°C) but should still flash the alarm code until the Acknowledge Alarm button
is pressed. If the alarm condition is still active, the HTC cannot start, it will flash
the alarm code again. If the alarm condition is not active, the display should return
to the normal default screen display and the HTC is ready to run.

Alarms place the control in “standby” mode. After the alarm is corrected and
acknowledged, cycle the heater Standby/Enable switch to “Standby” then back to
“Enable” to restart the process control.

C o d e

D e s c r i p t i o n

A l a r m L E D

A1

Process High Temperature

Solid Red

A2

Process Temperature Loop Break

Solid Red

A3

Process Heater Box High Temperature

Solid Red

A10

RTD Integrity

Solid Red

A39

EEProm Write Error-Internal Control

Solid Red

Board Problem

A49

Process Protection High Alarm

Solid Red

A50

Process Differential Alarm

Solid Red