B e f o r e B e g i n n i n g

You can avoid most problems by following the recommended installation and
maintenance procedures outlined in this User Guide. If you do have a problem,
this section will help you determine what caused it and how to fix it.

Before you start disassembling the HTC process air heater be sure to:

Diagnose causes from the control panel.

1

Press the Acknowledge Alarm button to silence the alarm.

2

Address the alarm message and fix the problem.

3

Move the heater switch from Enable to Standby.

4

Cycle the heater switch from Standby to Enable to restart normal con-

trol. If the alarm reappears the problem was not fixed.

If the alarm is a passive alarm you will see P in the screen title display.

If the alarm is a shut down alarm you will see A in the screen title
display.

Diagnose causes from the control panel.

You can locate any problem from the front of the heater.

Heaters

Startup /

Shutdown

For Startup:

1. With heaters in
Standby, turn on
blower or dryer.
2. Enable heaters.

For Shutdown:

1. Switch heaters to
Standby.
2. Wait 60 seconds
before turning off
blower or dryer.

Enable

Standby

Acknowledge
Alarm Button

Scroll
Button

6 - 2

l Tr o u b l e s h o o t i n g