Drying the Generator (Continued)

2. Disconnect Wires No. 4 from the Voltage Regulator.
3. Provide an external source to blow warm, dry air through
the generator. DO NOT EXCEED 185* F. (85* C.).
4. Start the generator and iet it run for 2 or 3 hours.

5. Stop the engine and retest Stator and Rotor insulation for
breakdown.

Page 1.3-2