Section 4.4- OPTIONAL REMOTE RADIATOR FAN

Some NP senes engine-generators are not equipped

with a unit-mounted radiator. The radiator on such units is

mounted at a remote location in the vehicle that houses the
generator. Such installations might require the following
options:

An electrically operated RADIATOR FAN, along with a

temperature sensor switch.

A squirrel cage type COMPARTMENT FAN which draws

cooling and ventilating air through the compartment housing
the generator.

Compartment Fan

The compartment fan (Figure 8) must be properly lo­

cated during installation. When running, it must draw cooling
and ventilating air through the generator compartment and
expel the air to the outdoors. The compartment fan is needed,
since an engine-driven fan Is not provided.

The compartment fan motor is connected to generator

AC output leads 11 and 22. When the generator is running
and AC voltage is available, the fan will operate.

A Remote Radiator Assembly

COMPONENTS:

Major components of a typical remote radiator and fan

include (a) the radiator, (b) the fan, (c) a thermostatic switch,
(d) mounting hardware, and (e) wiring harnesses. See Figure

10 on next page.

OPERATION:

See Figure 9, below. Battery voltage for fan operation is

always available to Tewrminal 30 of the Fan Relay (SR), via
a 14 amp fuse and Wire 13A. However, the fan relay normally-
open contacts are open and the fan Is NOT running. On
cranking and startup of the generator, an engine control
circuit board delivers 12 volts DC to the Thermostatic Switch
(TS) via Wire 14, Relay Coil, and Wire 243. If coolant temper­
ature is below approximately 180' F., the thermostatic switch
contacts will be open. As soon as coolant temperature In­
creases above 180' F., the switch contacts close and Wire

243 is grounded. Fan Relay (SR) then energizes, its normally-
open contacts close, and DC voltage is delivered to the FAN
via Wire 244. The fan is now powered and will run.

Figure 9. Remote Radiator Fan Operating Diagram

.244 .

^ 244

i

)

tt

L

FAN
RELAY

■ 13A .

NOTE: ThermottaUc switch contacts close above

2^3

^80"

F.; fan relay contacts are energised closed

when switch contacts close.

12VDC WITH

ENGINE RUNNING

"

only

,12 VDC FAN

POWER SUPPLY

- 14——

14 AMP

FUSE

THERMOSTATIC

7777777

Page 4.4-1