Dunkirk DWB Series User Manual

Page 12

Advertising
background image

12

WARNING

Burn and Scald Hazard. Safety relief vlave

could discharge steam or hot water during

operation. Install discharge piping per these

instructions. Failure to do so could result in

death or serious injury.

!

5.4 Safety Relief Valve

NOTICE

Boiler rated at 43.5 psig (.30MPa) maximum allowable

working pressure. Boiler provided with 30 psig

(.21MPa) safety relief valve.

• Install safety relief valve using pipe fi ttings provided with

boiler. See fi gure 7.

• Install safety relief valve with spindle in vertical position.

• Do not install shutoff valve between boiler and safety

relief valve.

• Install discharge piping from safety relief valve. See

fi gure 8.

• Use ¾” or larger pipe.
• Use pipe suitable for temperatures of 375°F (191°C)

or greater.

• Individual boiler discharge piping shall be independent

of other discharge piping.

• Size and arrange discharge piping to avoid reducing

safety relief valve relieving capacity below minimum

relief valve capacity stated on rating plate.

• Run pipe as short and straight as possible to location

protecting user from scalding and properly drain

piping.

• Install union, if used, close to safety relief valve outlet.
• Install elbow(s), if used, close to safety relief valve

outlet and downstream of union (if used).

• Terminate pipe with plain end (not threaded).

5 - HYDRONIC PIPING

Figure 7 - Safety Relief Valve & Air Vent

(Viewed from front of boiler)

1” MPT

Coupling 1”

NPT

Nipple 1” x 5”

Tee 1” x 1” x ¾”

Safety Relief

Valve

Street Elbow ¾”