13 - TROUBLE SHOOTING

Diagnostics

The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will fl ash indicating the

fault code.

There are faults that cause permanent shutdown (marked with the letter “A”): to restore operation just press the RESET

button (detail 6 - Section 10.4, Control, page 25) for 1 second or RESET on the optional remote timer control if installed;

if the boiler fails to start, it is necessary to fi rst eliminate the fault.

Other faults (marked with the letter “F”) cause temporary shutdowns that are automatically reset as soon as the value

returns within the boiler’s normal working range.

Table of faults

- List of faults

Fault
code

Fault

Possible cause

Cure

A01

No burner ignition

No gas

Check the regular gas fl ow to the boiler and that the air has
been eliminated from the pipes

Ignition/detection electrode fault

Check the wiring of the electrode and that it is correctly
positioned and free of any deposits

Faulty gas valve

Check the gas valve and replace it is necessary

Ignition power too low

Adjust the ignition power

A02

Flame present signal with burner
off

Electrode fault

Check the ionisation electrode wiring

Card fault

Check the card

A03

Overtemperature protection
activation

Heating sensor damaged

Check correct heating sensor positioning and operation

No water circulation in the system

Check the circulating pump

Air in the system

Vent the system

F05

The air pressure transducer does
not receive a suffi cient minimum
value within 25 seconds

Incorrect air pressure transducer wiring

Check the wiring

Flue not correctly sized or obstructed

Check the length of fl ue and that it is clean

A06

No fl ame after the ignition stage

Low pressure in the gas system

Check the gas pressure

Burner minimum pressure setting

Check the pressures

F10

Delivery sensor 1 fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted
Wiring disconnected

F11

DHW sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted
Wiring disconnected

F14

Delivery sensor 2 fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted
Wiring disconnected

A15

Air signal protection activation

Fault F05 generated 5 times in the last
15 minutes

See fault F05

F34

Supply voltage under 170V.

Electric mains trouble

Check the electrical system

F35

Faulty mains frequency

Electric mains trouble

Check the electrical system

F37

Incorrect system water pressure

Pressure too low

Fill the system

Sensor damaged

Check the sensor

F39

External probe fault

Probe damaged or wiring short circuit

Check the wiring or replace the sensor

Probe disconnected after activating the
sliding temperature

Reconnect the external probe or disable the sliding
temperature

A41

Sensor positioning

Delivery sensor detached from the pipe

Check correct heating sensor positioning and operation

F42

Heating sensor fault

Sensor damaged

Replace the sensor

F43

Exchanger protection activation.

No system H

2

O circulation

Check the circulating pump

Air in the system

Vent the system

A44

DHW sensor disconnected

Sensor disconnected

Check the correct positioning and operation of the DHW
sensor.

A48

Air signal protection activation

Fault F05 for 150 seconds

See Fault F05

F50

Modulation regulator fault

Wiring disconnected

Check the wiring

F51

Low water cutoff warning

Pressure too low

Fill the system

Low water cutoff damaged

Check the contact