Caution, Danger – Dunkirk DWB Series User Manual

Page 22

Advertising
background image

22

7 - GAS SUPPLY PIPING

CAUTION

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use

any phone in your building.

• Immediately call your gas supplier from a

neighbor’s phone. Follow gas supplier’s

instructions.

• If you cannot reach your gas supplier, call the fi re

department.

7.1 General

• Use piping materials and joining methods acceptable

to authority having jurisdiction. In absence of such

requirements:

• USA - National Fuel Gas Code, ANSI Z223.1/NFPA 54

• Canada - Natural Gas and Propane Installation Code,

CAN/CSA B149.1

• Size and install gas piping system to provide suffi cient

gas supply to meet maximum input at not less than

minimum supply pressure. See Table 5.

• Support piping with hooks straps, bands, brackets,

hangers, or building structure components to prevent or

dampen excessive vibrations and prevent strain on gas

connection. Boiler will not support piping weight.

• Use thread (joint) compound (pipe dope) suitable for

liquefi ed petroleum gas.

• Provide sediment trap up stream of gas valve.

• Install manual main shutoff valve outside of jacket. See

fi gure 16.

7.2

Conversion To LP

Refer to Gas Conversion Kit Instructions.

DANGER

Fire Hazard. Do not use matches, candles, open

fl ames, or other methods providing ignition source.

Failure to comply will result in death or serious

injury.

7.3

Leak Check Gas Piping

Pressure test boiler and gas connection before placing

boiler in operation.

• Pressure test over 1/2 psig (3.5 kPa). Disconnect

boiler and its individual gas shutoff valve from gas

supply system.

• Pressure test at 1/2 psig (3.5 kPa) or less. Isolate

boiler from gas supply system by closing manual gas

shutoff valve. See fi gure 16.

• Locate leakage using gas detector, noncorrosive

detection fl uid, or other leak detection method

acceptable to authority having jurisdiction. Do not use

matches, candles, open fl ames, or other methods that

can provide ignition source.

• Correct leaks immediately and retest.

Figure 15 Manual Main Gas Shutoff Valve

Outside Boiler Jacket

With Manufacturer Suggested Piping With Drip Leg

Manufacturer suggested gas piping with drip leg.

Gas Supply Pressure

Natural Gas

Min.

Max.

3.5" w.c.

(0.7 kPa)

14" w.c. (3.3

kPa)

Table 5 - Gas Supply Pressure

Nipple

¾” x 3” NPT

Tee ¾” NPT

Nipple ¾ x

3” NPT

¾” Pipe Cap

Gas

Connection

¾” Gas

Shutoff

Valve in ON

Postion

Nipple

¾ x 3”

NPT