Water system pressure adjustment

The fi lling pressure with system cold, read on the boiler

water gauge, must be approximately 11 psi.

If the system pressure falls to values below minimum, the

boiler control will activate fault F37.

Low system pressure fault

Once the system pressure is restored, the boiler will

activate the 120-second air venting cycle indicated on the

display by FH.

TEST mode (heating power = 100%)

Press heating buttons simultaneously for 5 seconds to

turn on TEST mode. The boiler will ignite at the maximum

heating power set as described in the following paragraph.

On the display, the heating and tap water symbols will

blink; alongside, it will show the heating power and the

ignition power respectively.

To turn off TEST mode, repeat the sequence for turning it

on.

10 - OPERATING INSTRUCTIONS