WARNING

Vent extending through exterior wall shall not

terminate adjacent to wall or below building

extensions such as eaves, balconies, parapets or

decks. Failure to comply could result in death or

serious injury.

!

Table 3 - Combustion Air and Vent Pipe Fittings

6 - COMBUSTION AIR AND VENT PIPING OF DIRECT VENT AND CATEGORY III

10.

If the horizontal vent must go through a crawl space or

other unheated space, the cool temperatures will likely

cause the fl ue gases to continuously condense inside

the vent pipe. Do not insulate the vent pipe. It must be

visible for monthly inspection. Insure that the vent pipe

is properly pitched away from the boiler, with no low

spots, so that condensate in the vent will drain away

from the boiler. An insulated enclosure or chase, with

access for inspection and servicing of the vent, may

be required to prevent freezing of liquid condensate.

Consult the vent pipe manufacturer’s instructions for

specifi c guidelines.

11.

At beginning of each heating season and monthly

during the heating season, check all vent pipes and

vent terminal to make sure there are no obstructions.

Periodically clean the screen in the vent terminal.

Equivalent Length of Venting Components:

5 ft. equivalent for a 3” 90° elbow.

2 1/2 ft. equivalent for a 3” 45° elbow.

Type

Item

Diameter

Min Lenght

Max Lenght

Material

Standards

Direct vent

Vent

3”

5 ft

65 ft

AL294C Stainless

Steel, Aluminum

UL1738,

ULC S636

Air intake

3”

5 ft

65 ft

Stainelss Steel,

PVC, CPVC, PP,

Aluminum

ANSI/ASTM

D2564, ANSI/

ASTM F493, UL

1738/ULC636-08

Category III

Vent

3”

5 ft

65 ft

AL294C Stainless

Steel, Aluminum

UL1738,

ULC S636