CPD 3000 Integration Guide

11


Table 1 LC Network UNVTfaults Variables Implemented on the CPD 3000

Network Variable

Type

Notes

nviLampValue

SNVT_switch

Primary control input. The level

translates to a 0-10V control signal with
the transform being subject to the values

configure in nciControlConfig defined
below. By default, 50% results in a 5V

control signal to the ballast, driver, or,

generator controlled by the CPD 3000.

nviStatReset

UNVTstatControl

Sets/initializes energy, runtime, and

error counts.

nvoControlData UNVTcontrolData

A structured variable describing all

current operating values and state of

the LC. This is described in the
following section.

nvoLampFb SNVT_switch

Feedback of the current
nviLampValue

. In normal operating

conditions, this value will reflect the
nviLampValue

. It may differ if the

heartbeat interval is exceeded and the
defaultLevel

differs from the value

in nviLampValue.

nvoLcStatus UNVTfaults

Feeds alarm logs only on change to

minimize the data requirement on the
IP network. The frequency of changes

to this variable is carefully managed

to conserve bytes consumed by data
logs.

nvoVersion

UNVTversion

A string describing the version of the

OLC application, such as 1.00.09.

UNVTcontrolData – nvoControlData

Details

The LC conserves power line bandwidth by reporting the operating state of the
LC in a single output network variable nvoControlData (UNVTcontrolData),
described in this section. Previous profile designs typically require three poll