CoolDownTm

 will extend this time.as

required when controlling certain lamp

types such as HPS. 

rampTm SNVT_time_sec

Controls how the LC ramps between level
transitions. Only used after the lamp is

ON to go between intermediate steps. The
CPD 3000 limits this value to a maximum

of 30s. (Default value – 1.5s)

supplyVoltage SNVT_volt

The nominal supply voltage for the fixture.
Used of voltage level alarms. (Default

value – 240V).

warmupTm unsigned

short

The number of minutes the LC allows the
fixture to warm up before allowing

dimming commands. During warm up, the

dimming commands are deferred. If the
LC is set to go to 75% ON, the LC will set
the 0-10V signal to 10V for warmupTm
minutes before issuing the appropriate

dimming level. In LED applications, this

is typically 0. Any nviLampValue less
than 100% will be delayed while the LC is
in the state OLC_WARMUP. (Default value –
0s). This also delays power alarm

processing which is important in the case

of control of magnetic ballast technology.

coolDownTm unsigned

short

The number of minutes the LC will delay
commands to turn ON after the fixture has

been turned OFF. This is important for
improving certain lamp technology life

times. The CPD 3000 enforces a 10s

COOLDOWN to allow recovery of the
inrush protection circuit. This 10s

minimum is subject to change in the
future.
(Default value – 0s)

maxRcvTm SNVT_time_sec

If the LC fails to receive an update to
nviLampValue

for this time (0s default),

the LC will drive the lamp to the
defaultLevel

. The segment controller

should update nviLampValue up to three
times within this period. If the maxRcvTm
is 900s, the heartbeat rate of 300s should
be used by the segment controller. Note
that maxRcvTm = 0 means lights will
retain the last commanded value if the

SmartServer cannot communicate to the

device, or if it fails.

minPWM unsigned

long

It may be necessary to set the lowest 0-

10V signal to a value that can be used to
drive the controlled fixture. This value