CPD 3000 Integration Guide

19

controlled to defaultLev
(Default –0s; which means

HB checking is disabled)

nciPowerProfile UNVTpowerProfile

Defines the nominal power
at 0.5, 25, 50, 75, 100%

lamp
nviLampValue.value

.

Used to determine the

expected power draw using
linear interpolation for
nviLampValue.values

in

between steps defined in

the table.

nciLimits.powerLowFault SNVT_lev_cont

The percentage deviation
of expected power below
which the LowPower alarm
is triggered. (Default value
- 15%)

nciLimits.powerHighFault SNVT_lev_cont

The percentage deviation

of expected power above
which a HighPower alarm
is triggered. (Default
value - 15%).

nciLimits.voltageLow SNVT_lev_cont

The percentage deviation

below the configure
supplyVoltage

at which

the LowSupplyVoltage
alarm is triggered.

(Default value - 15%).

nciLimits.voltageHigh SNVT_lev_cont

The percentage deviation
above the configured
supplyVoltage

at which

the HighSupplyVoltag
alarm is triggered.

(Default value - 15%).

nciLimits.pfLow SNVT_pwr_fact

Power factor alarm point.
Power factor alarms are

only tested when the
controlled load is ON.

(Default value - .65)

nciLimits.rcvHb SNVT_time_sec

The rate at which the
segment controller is

expected to update
nviLampValue

. Best

practice is to set this value

at 3x shorter than
nciControlCfg.rcvTmo
(Default value – 0s).

nciLimits.highTemp SNVT_temp_p

The temperature above
which a high temperature

Advertising