Creating the cpd 3000 device on your smartserver – Echelon Lumewave CPD 3000 Lighting Controller User Manual

Page 23

Advertising
background image

CPD 3000 Integration Guide

23

E

WARMUP state timer expires OR commanded OFF

Updates to nviLampValue are
delayed until out of WARMUP.

F

COOLDOWN state timer expires AND (.defaultLev > 0
AND rcvTmo) OR command ON

Occurs when .warmupTm is > 0

G

WARMUP state timer expires AND (commanded ON

OR (rcvTmo AND .defaultLev > 0))

H

command OFF OR (rcvTmo AND .defaultLev == 0)

COOLDOWN for at least 10 for
inrush circuit recovery

I

.warmupTm == 0 AND (Command ON OR (rcvTmo
AND .defaultLev > 0)

During the transition from OFF to ON, the CPD 3000 drives the 0-10V control

signal directly to the final level at the time the load switching relay is engaged. If
the CPD 3000 is configured with a nciControlCfg.warmupTm > 0, the control
signal is driven to the 100% level, and finally the level defined by
nviLampValue.value

after the warmupTm has completed. Changes in lamp level

while the load is ON are applied as a smooth ramp over the time specified by
nciControlCfg.rampTm

(0 – 30.0 s, 0.1s steps). The transition to OFF will sweep

the 0-10V control to the minimum level before releasing the load switching relay.

Creating the CPD 3000 Device on your SmartServer

To create a L

ON

W

ORKS

device, follow these steps. For more information, see

Creating LonWorks Devices in Chapter 5 of the SmartServer User’s Guide.


If you are using the SmartServer in Standalone mode, copy the following files to

the SmartServer flash disk:

• Copy the external interface (XIF) files of the devices to be managed by the

SmartServer to the root/LonWorks/import folder on the SmartServer flash
disk.

• Copy the device resource files to the root/LonWorks/types/user folder.

• If you plan on upgrading the devices using the SmartServer, you need to copy

the devices’ application image files to the root/LonWorks/import folder.

• Reboot the SmartServer.