Cpd 3000 control sequence – Echelon Lumewave CPD 3000 Lighting Controller User Manual

Page 22

Advertising
background image

22

The CPD 3000 uses the nciPowerProfile table to define the expected power at
five equally spaced nviLampValue.values (.5%, 25%, 50%, 75%, 100%) once the
minPWM

and maxPWM CP fields have been established.


Note that nviLampValue.state is set to -1 at powerup/reset.

CPD 3000 Control Sequence

The CPD 3000 implements the state machine diagram depicted in figure 5 below.
The field nvoControData.LCstate reports the current active state for the
controller. To manage inrush current, the CPD 3000 uses an NTC Thermistor to

limit current inrush current commonly encountered with LED drivers and other
electronic ballasts. To be effective, the device needs a recovery time of 10s after

the load is switched ON. This means that power loss or reset will switch the load

OFF for 10s before turning the load ON. The configuration property field
nciControlCfg.cooldownTm

provides additional if required by the load under

control.

Figure 7. CPD 3000 State Diagram


Table 4. CPD 3000 Control State Transition Descriptions

Path

Condition

Comments

A Power-up

or

Reset

10s COOLDOWN minimum
enforced for inrush limiter
recovery.

B

COOLDOWN state timer expires AND (command ON

OR .defaultLev > 0)

An unconfigured node will

follow this path FULL_ON level

C

COOLDOWN state timer expires AND (.defaultLev ==
0 AND rcvTmo) OR command OFF

D

(Command ON OR (.defaultLev > 0 AND rcvTmo))
AND .warmup > 0

Warmup state always drives
the control signal to the

configured high limit.