Network Cabling and Connections

The Model 42100 LPR-10 Router (TP/FT-10 to TP/FT-10) uses the TP/FT-10 channel

cabling scheme. The Model 42102 LPR-12 Router (TP/FT-10 to TP/XF-1250) uses a

different cabling scheme that is designed to handle high speed, 1.25Mbps

communications. This 1.25Mbps cabling scheme is described in a later section.

System Performance and Cable Selection - TP/FT-10 Channel

The system designer may choose a variety of cables, depending on cost, availability,

and performance. Currently, Echelon has documented system performance on the

cable types shown in tables 3.1 and 3.2. Up to 64 devices may be connected to each

channel; one or more Model 42100 LPR-10 Routers may be used to increase the

number of devices and cable distance. Network performance specifications assume

that the average wire temperature is +55°C, although individual segments of wire

may be as hot as +85°C.

The free topology transmission specification includes two components which must

both be met for proper system operation. The distance from each LonPoint module,

network interface, or third party device to all other devices, and the distance from

each LonPoint module, network interface, or third-party device to the Model 44100

Terminator, must not exceed the maximum node-to-node distance. If multiple paths

exist, e.g., a loop topology, then the longest path should be used for the calculations.

The maximum total wire length is the total amount of wire connected per channel.

Table 3.1 Free Topology Specifications

Maximum
node-to-node
distance

Maximum total
wire length

Wire Diameter

AWG/mm

Belden 85102

500 meters

500 meters

16AWG/1.3mm

Belden 8471

400 meters

500 meters

16AWG/1.3mm

Level IV, 22AWG

400 meters

500 meters

22AWG/0.65mm

JY (St) Y 2x2x0.8

320 meters

500 meters

20.4AWG/0.8mm

TIA Category 5

250 meters

450 meters

24AWG/0.51mm