Echelon LonPoint Module User Manual

Page 64

Advertising
background image

4-28

Installation and Wiring of Base Plates

Table 4.4 Type 2D Base Plate Terminal Block Connections

Terminal Number

Function

1 -4

Network A

5

Cable shield, if used, internally connected to terminal 14

6 - 9

Power

10 and 12

None

Jumpered together internally, may be used to land extra wires

11 and 13

None

Jumpered together internally, may be used to land extra wires

14

Cable shield, if used, internally connected to terminal 5

15 - 18

Network B

Two sets of screws are provided for both the power and network wiring connections.

These connections are internally jumpered on the Type 2D Base Plate PCB to

provide continuity of the network and power wiring, even if no LonPoint module is

installed, as shown in figure 4.26. This feature permits the Base Plate wiring to be

pre-installed and the network and power circuits checked for continuity throughout

the installation, before a single LonPoint module is ever installed. This feature also

prevents network and power interruptions as a result of hot-swapping LonPoint

modules during commissioning or service operations. Finally, providing two sets of

screw terminals permits incoming and outgoing to be landed at separate screw

terminals without the need to insert more than one wire in any given screw

terminal.

1 2 3 4 5 6 7 8 9

Network

16-30VAC or VDC

Figure 4.26 Base Plate Power and Network Wiring Connections