Do-10 module software settings, Installing the do-10 module – Echelon LonPoint Module User Manual

Page 83

Advertising
background image

LonPoint Hardware Guide

7-5

EMI

FCC A, CE Mark

Safety agency

UL 916

Function Blocks

Node object (1), digital output open-loop actuator objects (4),
digital encoder controller objects (2), analog function block
controller objects (2), type translators (6)

Software Configuration

Wide variety of L

ON

M

ARK

Standard Configuration Parameter

Types supported by direct memory read/write function of LNS
compatible network management tools

DO-10 Module Software Settings

The software settings of the DO-10 module are described in the LonPoint

Application and Plug-In Guide

Installing the DO-10 Module

Installation of the DO-10 module involves the following steps:

1. Ensure that the Base Plate has been wired and installed correctly, and is

securely fastened to the electrical enclosure.

2. Check for continuity on all network and power wiring. Ensure that the correct

actuators are connected to the correct Base Plate I/O terminals.

3. Make certain that all network channels are terminated with the correct number

and type of Terminator.

4. Insert the DO-10 module into Base Plate by aligning the network access jack on

the DO-10 with the arrow head on the Base Plate (the arrow should point in the

direction of the jack), and then pressing firmly to ensure that the module is

properly seated in its mating Base Plate connector.

5. The DO-10 module can be hot-plugged: there is no need to disconnect power

when installing the module. If power is present then the Power LED will

illuminate continuously. If power is not present then the Power LED will remain

off. The hand/off/auto switches will not function unless the DO-10 module is

powered.

6. Securely attach the DO-10 module to the Base Plate by screwing the two

Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts

in the Base Plate. Use approximately 4 lbs. in/0.5Nm torque on the screws.

7. Follow the node configuration procedure described in the LonPoint Application

and Plug-In Guide

to configure the software in the DO-10 module.

8. See Troubleshooting for assistance with improper DO-10 module operation.