Installing the DIO-10 Input/Output Modules

6-5

DIO-10 Digital Input/Output Module Software Settings

The software settings of the DIO-10 are described in the LonPoint

Application and Plug-In Guide.

DIO-10 Digital Input/Output Module Firmware

The DIO-10 firmware contains the following function blocks: Digital

Input/Counter function block (2), Digital Output function blocks (2),

Analog function block (2), Digital Encoder function block (2), Type

Translator function block (4), Node Object (1).

See the LonPoint Application and Plug-In Guide for details on those

function blocks.

Installing the DIO-10 Digital Input/Output Module

Installation of the DIO-10 module involves the following steps.

1. Ensure that the Type 1 or Type 1D Base Plate has been wired and installed

correctly.

2. Check for continuity on all network and power wiring. Ensure that the correct

sensors are connected to the correct Base Plate I/O terminals.

3. Make certain that all network channels are terminated with the correct number

and type of Terminator.

4. Insert the DIO-10 module into the Base Plate by aligning the network access

jack on the module with the arrow head on the Base Plate (the arrow should

point in the direction of the jack), and then pressing firmly to ensure that the

module is properly seated in its mating Base Plate connector.

5. The DIO-10 module can be hot-plugged: there is no need to disconnect power

when installing the module. If power is present then the Power LED will

illuminate continuously. If power is not present then the Power LED will remain

off.

6. Securely attach the DIO-10 module to the Base Plate by screwing the two

Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts

in the Base Plate. Use approximately 4 lbs. in. (0.5Nm) torque on the screws.

7. Follow the node configuration procedure described in the LonPoint Application

and Plug-In Guide

to configure the software in the DIO-10 module.

8. See Troubleshooting for assistance with improper DIO-10 module operation.