6-4

Installing the DIO-10 Input/Output

Modules

Both digital inputs have internal pull-up resistors (2.43 K ) connected to

5V through a diode. This pull-up resistor allows the use of low-cost (non-

noble, metal-plated) contacts in external dry contacts (relays). The diode

prevents current flow through the pull-up resistor to the power supply

when the input is not a dry contact but a logic voltage above 5V. When the

input voltage is below 5V, the external electronics must sink current.

When the input voltage is above 5V, then the diode prevents the flow of

current through the pull-up resistor. For inputs above 5V, a separate

protection diode is forward biased through a 21.5K resistor. Table 6.3

details the sink (-)/source (+) currents required of the external electronics

at various input voltages.

Table 6.3 Sink/Source Currents

Input Voltage

Input Current

0V

-1.7mA

3V

-0.5mA

5V

0mA

10V

+0.2mA

20V

+0.65mA

32V

+1.21mA

Note: The two inputs on the DIO-10 are isolated from the power supply
and from the network, but are not isolated from each other. If the
installation requires that the inputs be isolated from each other, additional
LonPoint modules should be used.

Table 6.4 LonPoint DI-10 Digital Input Module Specifications

Function

Description

Processor/memory

Neuron 3150 Chip, 10MHz, 56K flash memory

Service function

Recessed service switch, service LED, power/wink LED.
Dual tear-off bar-code Neuron ID self-adhesive tag for
application to red-line drawings in the field

I/O

2 digital inputs, 5,12,24,31V or dry contact. Up to 20kHz
frequency measurement; 2 relay outputs (each has one Form A
and one Form B contact with a common wiper) rated at 2A
continuous 6A surge at 30 VAC or 24VDC. Separate status
LEDs for each input

I/O isolation

100V, transformer isolation. Inputs are isolated from the input
power and the network but not from each other.

Transceiver type

FTT-10A with blocking capacitors for compatibility with link
power channel

Network connector

Phone plug connector accessible from front panel

Input power

16-30VAC or VDC @ 4.75VA, internally isolated power supply

Mounting

Type 1 or Type 1D Base Plate

Temperature

-40 to +85°C, operating and non-operating