LonPoint Hardware Guide

4-27

Figure 4.25 Mounting Hole Pattern Dimensions for Type 2D Base Plates

Connecting Wiring

Route all network and power cabling to the pertinent screw terminals located at the

top and bottom of the Base Plate. It is good practice to separate any nearby

input/output cabling as much as possible from the network and power cabling,

especially if low-level analog signals are being supervised.

Strip the cable jacket and wire conductors. The base plate screw terminals will

accept 24AWG (0.5mm) to 12AWG (2.2mm) wire, which should be stripped to a

length of 0.32" (8mm). Although not required, it may be useful to use a soldering

iron to tin the stripped lengths of any stranded wire to prevent fraying and

inadvertent contact with adjacent terminals. Identifying screw terminal numbers

are conveniently located both above and below each screw terminal. Symbols and/or

language identifying the function of the screw terminals also are provided.

Note that terminals 1 to 9 are numbered from left to right, but terminals 10 to 18

are numbered from right to left.

The optimum tightening torque for the screw terminals is approximately 4 pounds

(0.5Nm). The ideal flathead screwdriver tip width is 3/32" (2.5mm).