Echelon Mini FX User Manual

Page 70

Advertising
background image

Mini FX User's Guide

57

Note: The Mini FX Application is an OpenLDV application; therefore, it cannot

share a network interface with other L

ON

W

ORKS

applications. This means that when

the Mini FX Application is attached to a network interface, network tools such as the

LonMaker tool cannot use that network interface at the same time. To make the
network interface available to other applications, you must close the Mini FX

Application.
Conversely, the Mini FX Application cannot use a network interface that is currently
attached to another L

ON

W

ORKS

application. If you try to attach the Mini FX

Application to a network interface that is already connected, the following dialog

opens.

To make a connected network interface available to Mini FX Application, you must

close any L

ON

W

ORKS

applications using that network interface. If you are using the

LonMaker tool, you can also alternatively detach the application from the network

interface by clicking LonMaker, clicking Network Properties, clicking the
Network Interface tab, and clearing the Network Attached box, and then

clicking OK.
To use the Mini FX Application with network tools while avoiding network interface
conflicts, follow these guidelines:
• Use the network tool to download device applications that you have compiled

with the Mini FX Application into the target device, and to test that target

device.

• Use a separate network interfaces for the network tool and the Mini FX

Application. For example, you can install two U10 USB Network Interfaces in

your computer, and use one for the network tool, and use the other for the Mini
FX Application.

3. Select the device into which the application image is to be downloaded. You can do

this in three ways: sending a service pin message from the device, manually adding
a device, or selecting a previously registered device or a device automatically

discovered through the ISI protocol.
• To send a service pin message to register the device and select it, follow these

steps:

a. Press the Service button on the device. For the FT 5000 EVB or PL 3150/PL

3170 EVB, the Service button is a black button that is located along the right

side of the board and is labeled “Service”.

b. The Service Pin Message dialog opens. The Neuron ID of the device

appears in the Neuron ID box and its program ID in the Program ID box.

Advertising