5.2.4 Alarm Set Points

The

PID-G

UARD

alarm set points can be changed within limits.

To change any of the three alarm points:

Enter the maintenance menu as shown in Figure 7

PID-G

UARD

Maintenance Menu flow chart.

1.

Press the

M

ENU

button until to display Alarm1 is displayed.

2.

Press the

S

ELECT

button to initiate alarm set point change

3.

Press the

M

ENU

button to change the digit indicated by the underscore cursor

4.

Press the

S

ELECT

button to move the cursor to the next digit

When last digit is entered the

PID-G

UARD

will advance to the next menu

5.

Press the

M

ENU

button to advance to the next menu

Example of Alarm Set Point menus:

5.2.5 Span Set

The

PID-G

UARD

4-20mA output full scale span range can be changed within limits.

To change the span range:

Enter the maintenance menu as shown in Figure 7

PID-G

UARD

Maintenance Menu flow chart.

1.

Press the

M

ENU

button until to display Span is displayed.

2.

Press the

S

ELECT

button to initiate the mA Span menu

3.

Press the

M

ENU

button to change the digit indicated by the underscore cursor

4.

Press the

S

ELECT

button to move the cursor to the next digit

When last digit is entered the

PID-G

UARD

will advance to the next menu

5.

Press the

M

ENU

button to advance to the next menu

Example of mA Span menu:

Default mA Span

4mA

20mA

0 ppm

50 ppm

Alarm1

M

ENU

Alarm2

M

ENU

Alarm3

S

ELECT

S

ELECT

S

ELECT

0020

0005

0005

0010

0010

To change Alarm set points:
Press Menu button until Alarm to be changed is displayed
Press Select button to display the set point

The M

ENU

button changes digit indicated by underscore

cursor
The S

ELECT

button locks underscored digit and moves to

next digit

If change is not within range display returns to first digit
If change is within range display moves to next menu

M

ENU

mA Span

M

ENU

S

ELECT

0050

To change mA Span set points:
Press Menu button until mA Span is displayed
Press Select button to display the set point

The M

ENU

button changes digit indicated by underscore cursor

The S

ELECT

button locks underscored digit and moves to next digit