Model scs-101 network interface card, Description, Installing the scs-101 – DMP Electronics Security Control Receiver SCS-1R User Manual

Page 15: Connecting the network, Led indicators, Scs-101 data jumper settings, Rxd and txd, Force cts, Installation, Scs-101 network interface card

Advertising
background image

Digital Monitoring Products

SCS-1R Installation Guide

10

INSTALLATION

Model SCS-101 Network Interface Card

Description

The SCS-101 Network Interface Card provides for a connection from a digital data network to a port on the SCS-1R

Receiver. Each card includes one eight-pin modular connector for digital data network connection. This allows

the SCS-1R Receiver to accept alarm and system messages over a network from DMP panels. Refer to the SCS-101

Installation Guide (LT-0320).

An optional PC software application, SCS-CTM Check-in Table Manager, is available to backup the SCS-101 records

of all supervised network accounts for up to 32 different SCS-101 line cards.

The SCS-CTM program is compatible

with SCS-101 Version 201 or higher. For complete operation information, refer to the SCS-CTM User’s Guide

(LT-0940). Contact DMP Customer Service to purchase a copy of the SCS-CTM Check-in Table Manager software.

SCS-101

Network Interface Card

TXD
RXD

RTS
CTS

DTR

TXC
RXC

Serial Input

Red

Black

J8

TXD RXD

2
3

3
2

J3

J4

J2

CLK

DCO

J5

FORCE

CTS

8-Pin Modular

Plug

Installing the SCS-101

Install the SCS-101 in any one of the five right-hand SCS-RACK positions (slots 1-5) with the card puller in the

up position. Connect the 10-position flat cable from the SCS-150 processor card. The line card number is

determined by the processor card cable it is connected to.
THE LIGHT BROWN (PIN 1) WIRE OF THE FLAT CABLE CONNECTOR MUST FACE UP ON THE LINE CARD.

Connecting the Network

Connect a UTP network cable to an available 10BaseT port on the network. Maximum line impedance is 100

Ohms.

The SCS-101 automatically communicates UDP or TCP with DMP panels, and iCOM

SL

Network Alarm

Communicators.

LED Indicators

The seven bi-color LEDs indicate the network interface card condition during various stages of communication. A

description of each LED is listed below:

TXD Transmit Data

RXD

Receive Data

RTS Ready To Send

CTS

Clear To Send

DTR Data Terminal Ready

TXC

*Transmit Clock

RXC *Receive Clock
* If the clock signal is present, both red and green segments of the LEDs light.

SCS-101 Data Jumper Settings

The SCS-101 data jumpers are pre-configured for NET at the factory.

RXD and TXD

The factory setting is Transmit Data (TXD) on pin #2 and Receive Data (RXD) on pin #3.

FORCE CTS

The jumpers are set vertically as the factory default. This allows the SCS-101 to tie the CTS and RTS data lines

together.