System overview, Description, Function – DMP Electronics Security Control Receiver SCS-1R User Manual

Page 7: Character lcd membrane keypad, Printer, Additional messages, Hour recall tests, Line capacity, Opening and closing signals

Advertising
background image

Digital Monitoring Products

SCS-1R Installation Guide

2

INTRODUCTION

System Overview

Description

The SCS-1R Security Control Receiver system from DMP is a full featured digital dialer and data network capable

alarm receiver. The receiver provides a 32-character LCD display for viewing incoming messages and a built-in

membrane keypad for acknowledging messages and configuring the SCS-1R system.

Function

The SCS-1R Receiver system provides central stations with computerized monitoring of DMP panels. Features of

the SCS-1R include automatic alarm, trouble, and supervisory account message logging on a local printer including

the date and time of their occurrence. The SCS-1R also provides an output to most security automation software

packages.

32-Character LCD Membrane Keypad

The built-in LCD display and Membrane Keypad add flexibility to the SCS-1R system by allowing the operator to

view alarm messages before acknowledging them from the built-in Membrane Keypad. A typical alarm message

includes the account number, zone name, and alarm type with the time and date of the occurrence. Alarm

messages display on the LCD and print to the local printer.

Printer

Routine messages print without the need of operator response while non-routine messages print and display on

the LCD for operator acknowledgment.
Note: UL central station applications must use a serial printer that is listed for Fire Protective Signaling Systems.

Additional Messages

Other messages transmitted to the SCS-1R by DMP panels include:

• Zone bypasses and resets by name and number including the name of the person making the change
• Schedule changes including the name of the person making the change
• Trouble and Restoral message by zone name and number
• Door access reports including the user name and the number of the door being accessed

The Printout Explanation section of this guide provides a description of the SCS-1R alarm and activity messages

that print and display.

24-Hour Recall Tests

The automatic recall test from a digital dialer account must be tracked manually or with a listed automation

system. The SCS-1R Receiver does not automatically indicate a delinquent recall test. Failure to receive a signal

from a Digital Alarm Communicator Panel (DACT) over a 24-hour period is handled by the automation system.

Line Capacity

The SCS-1R Receiver accommodates up to eight line cards. The account range for Digital Dialer panels is 1 to

65,535.
To select the communication type used on each incoming line, refer to Line Card Programming section of this

guide.

Number of Standard or Encrypted Line Security Network Accounts

The maximum number of accounts with standard or encrypted line security and substitution using 6 minute

checkin that can be received by a single SCS-101 or SCS-104 Line Card is 3200.

Opening and Closing Signals

The total capacity of opening or closing signals per SCS-1R Receiver, limited by automation system using 19200

baud and acknowledgement speed of 100 milliseconds, is 300 per minute.

Compliance Instructions

For applications that must conform to a local authorities installation standard or a National Recognized Testing

Laboratory certificated system, please see the the Listed Compliance Specifications section near the end of this

guide for additional instructions.

Advertising