Cirbus, Cirbus instructions list – CIRCUTOR QNA500 series User Manual

Page 101

Advertising
background image

POWER QUALITY ANALYZER QNA500 8IO

QNA500 8IO Instruction manual

101 / 111

11.4.- CIRBUS

This is a CIRCUTOR proprietary protocol. It is a protocol with an ASCII format and query-response
based exchange. This protocol can send queries to the QNA500 analyzer, for example, query related
to on-line values, configuration values or communications-related parameters.
The instructions of this protocol are attached to the corresponding appendix of this manual.

The following port must be used when establishing communications through the Ethernet port: 10002

11.4.1.- CIRBUS INSTRUCTIONS LIST

A standard Cirbus message has the following format:

#npPPPPxxx^J

Where:

np: peripheral number in decimal places (00 to 99).
PPPP:

read or write password (def. 0000).

xxx: command.

There are 4 types of response.
#npACK
#npERR
#npBUSY
#npxxxxxxxxxxxxxxxxx

The following functions are implemented in this protocol:

1. Version and sub-version

P:

#np0000VEX^J

R:

#np1p340C

2. Reset

P:

#np0000INI^J

R:

#npACK

3. Write UTC

P:

#np0000WUT0^J ó #np0000WUT1^J

(BASE)

R:

#npACK ó #npERR

P:

#np0000WUT0^J ó #np0000WUT1^J

(QNA500)

R:

#npBUSY repeat the question until #npACK or #npERR is received

4. Read battery disconnection time

P:

#np0000RTD^J

R:

#np0600 => 600 seconds

5. Write battery disconnection time

Advertising