Instruction manual cvm-c10, Power supply v, L1 l2 l3 – CIRCUTOR CVM-C10 Series User Manual

Page 17

Advertising
background image

3�4�6�- Measuring Three-Phase Networks with a 3-wire connection and transformers

with an ARON connection, CVM-C10-ITF, CVM-C10-MC and CVM-C10-mV models�

Measurement system:

Power

Supply

V

L1

V

L2

V

L3

L1

L2

L3

POWER SUPPLY

INPUTS

A

(+) B(-)

GND

RS485

S1

S2

S1

S2 S1

S2

L1

P1

P2

L2

L3

300V ~

Ph-N

Ph-Ph

520V ~

N

V

L3

L2

V

L1

V

P1

P2 P1

P2

I1 I2

OUTPUTS

Rc R2 R1

Tc T2 T1

S0- S0+ S0+

V

L1

V

L2

V

L3

a

b

A

B

a

b

A

B

S1

S2

P1

P2

S1

S2

P1

P2

LOAD

Figure 8: Three-Phase measuring with a 3-wire connection and transformers with an ARON connection, CVM-C10-

ITF, CVM-C10-MC and CVM-C10-mV models�

CVM-C10-ITF model:

The transformer secondary value must be 5A or 1A

CVM-C10-MC model:

The MC transformer secondary value is set to 0.250 A (fixed value)

CVM-C10-mV model:

The transformer secondary value must be 0.333 V

17

Instruction Manual

CVM-C10

Advertising