3.2.- INSTALLATION

The unit will be installed on a panel (92

+0.8

x 92

+0.8

mm panel drill hole, in compliance with DIN

43700). All connections are located inside the electric panel.

Terminals, opening covers or removing elements can expose parts that are haz-

ardous to the touch while the unit is powered. Do not use the unit until it is fully

installed.

The unit must be connected to a power circuit that is protected with gl (IEC 269) or M type fuses

with a rating of 0.5 to 2 A. It must be fitted with a circuit breaker or equivalent device, in order to

be able to disconnect the unit from the power supply network.

The power and voltage measuring circuit must be connected with cables that have a minimum

cross-section of 1mm

2

.

The secondary line of the current transformer will have a minimum cross-section of 2.5 mm

2

.