CIRCUTOR CVM-C10 Series User Manual

Page 77

Advertising
background image

(

Continuation

) Pulse outputs (CVM-C10-ITF CVM-C10-MC and CVM-C10-mV)

Maximum frequency

16 impulses / sec

Pulse width

30 ms to 500 ms (Programmable)

Relay outputs

Quantity

2

Max� voltage open contacts

250 V ~

Maximum current

6 A

Maximum switching power

1500 W (AC1)

Electrical life (250 VAC / 5A)

60x10

3

cycles

Mechanical life

10x10

6

cycles

Digital inputs

Quantity

2

Type

NPN Potential free contact

Insulation

optoisolated

Communications

Modbus RTU

BACnet

Bus

RS-485

MS/TP

Protocol

Modbus RTU

BACnet

Baud rate

9600 - 1920

Stop bits

1 - 2

1

Parity

without - even - odd

without

User interface

Display

LCD Custom COG

Keyboard

Capacitive, 3 keys

LED

3 LED

Environmental features

Operating temperature

-5ºC... +45ºC

Storage temperature

-10ºC ... +50ºC

Relative humidity (non-condensing)

5 ... 95%

Maximum altitude

2000 m

Protection degree

IP31

Front panel: IP51 (IP64 with accessory)

Mechanical features

Dimensions ( Figure 26)

96.7x96.7x62.5 mm

Weight

330 gr

Surround

Self-extinguishing V0 plastic

Attachment

Panel

Standards

Safety of electronic measuring units

UNE EN 61010: 2010

Electromagnetic compatibility (CEM)� Part 6-3: Generic standards�

Emission standard for residential, commercial and light industry

environments�

UNE EN 61000-6-3:2007

Electromagnetic compatibility (CEM)� Part 6-1: Generic standards�

Immunity in residential, commercial and light industry environments UNE EN 61000-6-1:2007
Coordination of the insulation of units installed in low voltage sys-

tems (networks)�

IEC 664:2007

77