Installation (for qualified installers only), Clearances – Avalon Firestyles 34 DVL User Manual

Page 12

Advertising
background image

12

Installation (for qualified installers only)

© Travis Industries

4140813

100-01294

Clearances

Due to the high temperature of the heater, it should be located out of traffic and away from furniture and
draperies.

Minimum

Clearances

k Sidewall to Insert

4"
102mm

l Side Facing

(non-combustible)

4"
102mm

m Top Facing*

(non-combustible)

35.5"
902mm

n Mantel*

(combustible or
non-combustible)

35.5"
902mm

x Hearth Extension

(3-Piece Panel)

1.25"
32mm

x Hearth Extension

(1-Piece Panel)

0"
0mm

* Measured from the base of the insert.
NOTE: the non-combustible top facing
must extend 35.5” (902mm) above the
base of the insert or to the bottom of the
mantel (whichever is less).

Mantel Clearances

The maximum mantel depth is 12” (305mm).

NOTE: The combustible area above the facing must not protrude more than 3/4" (20mm) from the facing.
If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.

Side

Wall

Combustible or Non-Combustible Mantel

Combustible Top Facing

Non-Combustible

Facing

l

k

x

n

m

Mantel Height

Above Base of Insert (n)

36"(915mm)

35"(889mm)

34"(864mm)

33"(839mm)

37"+(940mm+)

32"(813mm)

31"(788mm)

0" 1" (26mm)

2" (51mm)

8" (204mm)

7" (178mm)

6" (153mm)

5" (127mm)

4" (102mm)

3" (77mm)

9" (229mm)

10" (254mm)

11" (280mm)

12" (305mm)

Maximum Mantel Depth