Installation – Avalon Firestyles 564 HO GS2 Installation User Manual

Page 32

Advertising
background image

32

Installation

(

for qualified installers only)

32

Travis Industries

4150330

100-01408

Facing Requirements

 The included fiber board is required and must remain attached to the fireplace (see “a” below).
 Non-combustible facing must extend 3” (77mm) above the face of the fireplace (see “c” below).

Drywall or other combustible may not be place on top of this non-combustible area.

 Drywall (or other combustible) may be placed above the non-combustible facing (see “b” below) and

to the sides and below the fireplace face. This combustible facing must be a minimum 3” (77mm)
above the face of the fireplace (see “b” below).

 Tile or other non-combustible facing may be placed along the perimeter of the fireplace face, but must

not extend over the glass/grill opening (see “d”). This area must remain open to allow for glass frame
removal and air flow.

Drywall Installation

(a) Fiber Board (included with fireplace)

(c) Tile (or other non-combustible)

(b) Drywall (or other combustible)

(d) Perimeter of Fireplace (may be covered)

c

b

b

c

a

b

b

d

3” (77mm)

a

}

Advertising