Basler Electric BE1-50/51B User Manual

Page 15

Advertising
background image

9252000991 Rev R

BE1-50/51B General Information

1-3

Table 1-1. BE1-50/51B Overcurrent Relays, One Ampere CT Secondary, 50/60 Hz

Model Number

Case Style

SW3-3 Selects

Sensing Input Range (Amps)

TIME

INST

BE1-50/51B-101

A1

0.2 Second Delay

0.1 - 3.18

0.2 - 19.8

BE1-50/51B-201

A1

Curve Set

0.1 - 3.18

0.2 - 19.8

BE1-50/51B-102

S1 (Projection Mount)

0.2 Second Delay

0.1 - 3.18

0.2 - 19.8

BE1-50/51B-202

S1 (Projection Mount)

Curve Set

0.1 - 3.18

0.2 - 19.8

BE1-50/51B-103

S1 (Semi-Flush Mount)

0.2 Second Delay

0.1 - 3.18

0.2 - 19.8

BE1-50/51B-203

S1 (Semi-Flush Mount)

Curve Set

0.1 - 3.18

0.2 - 19.8


Table 1-2. BE1-50/51B Overcurrent Relays, Five Ampere CT Secondary, 50/60 Hz

Model Number

Case Style

SW3-3 Selects

Sensing Input Range (Amps)

TIME

INST

BE1-50/51B-105

A1

0.2 Second Delay

0.5 - 15.9

1.0 - 99.0

BE1-50/51B-205

A1

Curve Set

0.5 - 15.9

1.0 - 99.0

BE1-50/51B-106

S1 (Projection Mount)

0.2 Second Delay

0.5 - 15.9

1.0 - 99.0

BE1-50/51B-206

S1 (Projection Mount)

Curve Set

0.5 - 15.9

1.0 - 99.0

BE1-50/51B-107

S1 (Semi-Flush Mount)

0.2 Second Delay

0.5 - 15.9

1.0 - 99.0

BE1-50/51B-207

S1 (Semi-Flush Mount)

Curve Set

0.5 - 15.9

1.0 - 99.0



NOTE: 100 series relays (e.g. - BE1-50/51B-105) have the integrating reset function when there is

adequate input current to power the relay. 200 series relays (e.g. - BE1-50/51B-205) have the integrating

reset function even when the input current falls to zero.

Advertising