Test procedure for five ampere units, Time pickup test, Inst pickup test – Basler Electric BE1-50/51B User Manual

Page 47: Time dial test, Test procedure for five ampere units -3, Time pickup test -3, Inst pickup test -3, Time dial test -3

Advertising
background image

9252000991 Rev R

BE1-50/51B Testing

5-3

NOTE

When testing TIME overcurrent functions, INST PICKUP settings of 00 will

affect the calibration of the TIME functions. TIME PICKUP settings of 00 also

affect INST functions.

Test Procedure for Five Ampere Units

Perform preliminary setup:

TIME Pickup Test

Connect test setup as shown in Figure 5-1.

Ensure that SW3 switches are set correctly: SW3-1 for operating frequency, SW3-2 to OFF (no

instantaneous delay), SW3-3 to OFF (no instantaneous delay (100 series relays) or ABB type

curves selected (200 series relays)), and SW3-4 to OFF (selects instantaneous reset).

Set TIME DIAL to 0.0.

Set CURVE to S

Set TIME PICKUP to 0.5.

Set INST PICKUP to 90.

Step 1. Slowly increase current to terminals 8 and 9. ACTIVE/PICKUP LED should turn RED at a

maximum input current of 0.550 ampere.

Step 2. Decrease input current until ACTIVE/PICKUP LED turns GREEN then OFF.
Step 3. Set TIME PICKUP to 2.2.
Step 4. Slowly increase current to terminals 8 and 9. ACTIVE/PICKUP LED should change from GREEN

to RED at an input current of 2.131 to 2.269 amperes.

Step 5. Decrease input current until ACTIVE/PICKUP LED turns GREEN then OFF.

Perform preliminary setup:

INST Pickup Test

Connect test setup as shown in Figure 5-1.

Ensure that SW3 switches are set correctly: SW3-1 for operating frequency, SW3-2 to OFF (no

instantaneous delay), SW3-3 to OFF (no instantaneous delay (100 series relays) or ABB type

curves selected (200 series relays)), and SW3-4 to OFF (selects instantaneous reset).

Set TIME DIAL to 0.0.

Set CURVE to S

Set TIME PICKUP to 15.1.

Set INST PICKUP to 01.

Step 1. Slowly increase current to terminals 8 and 9. INST contacts should close at an input current of

0.955 to 1.045 amperes.

Step 2. Decrease input current until INST output contacts open.
Step 3. Set INST PICKUP to 08.
Step 4. Slowly increase current to terminals 8 and 9. INST contacts should close at an input current of

7.815 to 8.185 amperes.

Step 5. Decrease input current until INST output contacts open.

Perform preliminary setup:

Time Dial Test

Connect test setup as shown in Figure 5-1.

Ensure that SW3 switches are set correctly: SW3-1 for operating frequency, SW3-2 to OFF (no

instantaneous delay), SW3-3 to OFF (no instantaneous delay (100 series relays) or ABB type

curves selected (200 series relays)), and SW3-4 to OFF (selects instantaneous reset).

Set TIME DIAL to 4.5.

Set CURVE to S