Target test, Manual trip test, Target test -4 – Basler Electric BE1-50/51B User Manual

Page 48: Manual trip test -4

Advertising
background image

5-4

BE1-50/51B Testing

9252000991 Rev R

Set TIME PICKUP to 1.0.

Set INST PICKUP to 90.

Step 1. Prepare to apply 1.5 amperes input current to terminals 8 and 9 and record the elapsed time from

when current is applied until TIME output contacts close.

Step 2. Apply the current (step from 0 to 1.5 amperes) and record the elapsed time. Elapsed time should

be 1.754 to 2.084 seconds. (This tolerance is greater than ±2 % because it is the accumulation of

both pickup and timing tolerances.)

Step 3. Remove input current.

Perform preliminary setup:

Integrating Reset Test (Applicable Only to 200 Series Relays)

Connect test setup as shown in Figure 5-1.

Ensure that SW3 switches are set correctly: SW3-1 for operating frequency, SW3-2 to OFF (no

instantaneous delay), SW3-3 to OFF (no instantaneous delay (100 series relays) or ABB type

curves selected (200 series relays)), and SW3-4 to ON (selects integrating reset).

Set TIME DIAL to 4.5.

Set CURVE to I.

Set TIME PICKUP to 1.0.

Set INST PICKUP to 90.

Step 1. Set voltage source to provide a target current of 1.0 ampere.
Step 2. Read all of Step 3 before beginning Step 3.
Step 3. Apply 4.0 amperes input current to terminals 8 and 9. After the unit trips, remove the input current

for 20 ±0.25 seconds, then reapply the 4.0 amperes input current. Record the elapsed time from

the re-application of input current to the output retrip.

Result: Elapsed time should be 1.55 ±0.3 seconds.

Perform preliminary setup:

Target Test

Connect test setup as shown in Figure 5-2.

Ensure that SW3 switches are set correctly: SW3-1 for operating frequency, SW3-2 to OFF (no

instantaneous delay), SW3-3 to OFF (no instantaneous delay (100 series relays) or ABB type

curves selected (200 series relays)), and SW3-4 to OFF (selects instantaneous reset).

Set TIME DIAL to 4.5.

Set CURVE to S

Set TIME PICKUP to 1.0.

Set INST PICKUP to 01.

Step 1. Set voltage source to provide a target current of 1.0 ampere.
Step 2. Apply 5 amperes input current to terminals 8 and 9. Check that both TIME and INST targets

operate.

Step 3. Remove input current and reset targets.

Perform preliminary setup:

Manual Trip Test

Connect test setup as shown in Figure 5-2.

Ensure that SW3 switches are set correctly: SW3-1 for operating frequency, SW3-2 to OFF (no

instantaneous delay), SW3-3 to OFF (no instantaneous delay (100 series relays) or ABB type

curves selected (200 series relays)), and SW3-4 to OFF (selects instantaneous reset).

Set TIME DIAL to 4.5.

Set CURVE to S

Set TIME PICKUP to 1.0.

Set INST PICKUP to 01.