Target indicators, Output contacts, Resistive ratings – Basler Electric BE1-50/51B User Manual

Page 21: Inductive ratings, Aux output contact, Type tests, Environment, Target indicators -9, Output contacts -9, Aux output contact -9

Advertising
background image

9252000991 Rev R

BE1-50/51B General Information

1-9

Figure 1-5. Harmonic Rejection

Target Indicators

Gravity latched, manually reset targets indicate that current of 0.2 amperes or greater was present in the

trip circuit. Target coil resistance is less than 0.1 ohms and operate time is less than one millisecond. See

Output Contacts for maximum current rating.

Output Contacts

Output contacts are surge protected and rated as follows:

120/240 Vac ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3

amperes continuously, and break 5 amperes.

Resistive Ratings

125/250 Vdc ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3

amperes continuously, and break 0.3 ampere.

120/240 Vac, 125/250 Vdc ........ Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2

minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).

Inductive Ratings

AUX Output Contact

The AUX Output contact can be configured in the field using jumpers to select closing on either timed or

instantaneous trip. The AUX output contact is surge protected and has the same ratings as the output

contacts above.

Type Tests

Isolation ..................................... IEEE C37.90-2005

Transient Surge ......................... IEEE C37.90.1-2004

Radiated Interference ................ IEEE C37.90.2-2004

Electrostatic Discharge .............. IEEE C37.90.3-2006

Vibration ..................................... IEC 255-21-1

Shock and Bump ....................... IEC 255-21-2

Environment

Operating Temperature ............. –40°C to 70°C (–40°F to158°F)

Storage Temperature ................ –50°C to 70°C (–58°F to 158°F).