Outputs, Instantaneous and timed, Auxiliary – Basler Electric BE1-50/51B User Manual

Page 32: Outputs -2, Figure 3-1. functional block diagram

Advertising
background image

3-2

BE1-50/51B Functional Description

9252000991 Rev R

Outputs

System circuit breakers controlled by the output contacts can be manually tripped by applying a short

across the TIME or INST MANUAL TRIP front panel test points. Current flow in the trip circuit is indicated

by the operation of the target. The targets will not operate without adequate operating power for the relay.

Instantaneous and Timed

WARNING!

Trip circuit voltage is present at the front panel test points. When shorting the

test points, use insulated jumpers to avoid contact with these voltages.

The auxiliary output contacts can be configured by the user to close when the timed and/or instantaneous

trip occurs. With both jumpers installed (this is the factory setting) either the timed or instantaneous trip

closes the auxiliary contacts. Effective with unit revision S, in units 9252000100 through 9252000109, the

printed circuit board was changed. Now, the PCB for 100 and 200 series relays are similar. Users with

units before revision R may see Section 6, Relay Differences, for installing auxiliary output contact

jumpers.

Auxiliary




Figure 3-1. Functional Block Diagram

POWER

CT

SUPPLY

POWER

BRIDGE

CT

SIGNAL

TIME

SCALE

INST

SCALE

MUX

SW

SW

SW

SW

TIME

PICKUP

INST

PICKUP

SW

SW

SW

DOG

WATCH

SUPERVISOR

MICRO

51

50

TIME

DIAL

TIME

CURVE

50/60 Hz

INST DELAY

TP

TP

AUX

ISOLATION

TARGETS

MAGNETIC

ACTIVE/PICKUP

51

50

INPUT

GND

D1181-09

2

3

6

5

4

7

8

9

AND

A/D

CONVERTER

POWER-OFF

SENSING

SERIES 200 RELAYS ONLY

SW

RESET CHAR.

51

50