Specifications

BE1-50/51B electrical and physical specifications are listed in the following paragraphs.

Current Sensing Input

Continuous Current.................... 2.8 Aac

1 Ampere Unit

One Second Rating ................... 80 Aac

Continuous Current.................... 14 Aac

5 Ampere Unit

One Second Rating ................... 400 Aac

Time Overcurrent (51) Element

Setting the TIME PICKUP control at the minimum pickup setting (0.1 on the 1 ampere unit and 0.5 on the

5 ampere unit), places the relay in the most sensitive state and may be used as a safety setting.

Setting Range ............................ 0.1 to 3.18 Aac

1 Ampere Unit Pickup

Setting Increment ....................... 0.02 Aac

Accuracy .................................... ±2%, ±5 milliamperes at or above 0.1 ampere setting

Setting Range ............................ 0.5 to 15.9 Aac

5 Ampere Unit Pickup

Setting Increment ....................... 0.1 Aac

Accuracy .................................... ±2%, ±25 milliamperes at or above 0.5 ampere setting

Dropout occurs at 95% of pickup value.

Dropout

0.0 to 9.9 seconds in 0.1 second steps.

Timing Range

The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times

tap and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy

that is the sum of ±2%, ±25 milliamperes for 5 ampere units, and ±2%, ±5 milliamperes for 1 ampere

units.

Timing Accuracy

PU setting .................................. 5 amperes

Timing Accuracy Example (5 Ampere Unit)

Current Applied .......................... 6.5 amperes

+ Multiple Tolerance .................. 6.655 amperes

– Multiple Tolerance .................. 6.345 amperes

Time Curve ................................ E

Time Dial .................................... 5.0

Minimum time dial

using 6.655 amperes ............... 46.5470 seconds

Maximum time dial

using 6.345 amperes ............... 61.3968 seconds

Curve time using 6.5 amperes ... 53.1800 seconds

Nine inverse time functions and one fixed time function can be selected by the front-panel Curve switch.

Characteristic curves for the inverse and definite time functions are defined by the following equation.

Curve Characteristics

Where:

T

T

= time to trip in seconds

D = time dial setting

M = multiple of pickup setting

A, B, C, N, K = constants for the particular curve

K

BD

C

M

AD

T

N

T

+

+

=

-