Burden, 1 ampere unit, 5 ampere unit – Basler Electric BE1-50/51B User Manual

Page 20: Frequency response, Transient response, Harmonic response, Burden -8, Frequency response -8, Transient response -8, Harmonic response -8

Advertising
background image

1-8

BE1-50/51B General Information

9252000991 Rev R

Burden

Burden is non-linear. Figure 1-4 illustrates the device burden.

0.1 amperes ............................... Z = 120 Ω

1 Ampere Unit

1.0 ampere ................................. Z = 5 Ω

0.5 amperes ............................... Z = 4.8 Ω

5 Ampere Unit

5.0 amperes ............................... Z = 0.2 Ω

Figure 1-4. Burden Characteristics

Frequency Response

A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for

pickup.

Transient Response

<10% overreach with system time constants up to 40 ms.

Harmonic Response

Figure 1-5 shows that a relay set for 1 ampere pickup would pick up at 0.96 amperes with a current

containing 40% seventh harmonic. This corresponds to a 10:1 rejection ratio. Other conditions may be

evaluated in the same manner.