Advantages, Specifications, Time overcurrent (51) element – Basler Electric BE1-50/51B-244 User Manual

Page 12: Be1-50/51b-244 pickup, Dropout, Characteristic curves, Fixed timing, Reset, Instantaneous overcurrent a (50-a) element, Advantages -2

Advertising
background image

1-2

BE1-50/51B-244 General Information

9252000793 Rev C

Westinghouse CO type curves, and instantaneous or integrating reset characteristics. Switch location and

description is provided in Section 2.

Advantages

BE1-50/51B-244 overcurrent relays have many advantages over other overcurrent relays. The primary

advantages are:

Time characteristics are defined by equations and graphs

Field selectable time characteristics

Very low burden extends the linear range of the CTs

Self powered from the sensed current

Continuous automatic calibration

BE1-50/51B-244 overcurrent relays may be tested without removing the relay from the case. Shorting

contacts are provided for all current inputs when the connection plug is removed from the relay case.

Specifications

BE1-50/51B-244 electrical and physical specifications are listed in the following paragraphs.

Time Overcurrent (51) Element

Setting Range:

0.5 to 15.9 Aac

BE1-50/51B-244 Pickup

Setting Increment:

0.1 Aac

Accuracy:

Sum of ±2% and ±25 mAac

Dropout occurs at 95% of pickup value.

Dropout

Available curve types follow IEEE Standard C37.112 (1996) and emulate standard GE IAC,

Westinghouse CO, and BS142 curves. Appendix A, Characteristic Curves illustrates the available curves

and lists the applicable constants.

Characteristic Curves

Curve Types:

Short Inverse, Long Inverse, Definite Time, Moderately Inverse, Inverse,

Very Inverse, Extremely Inverse, BS142 Very Inverse, BS142 Extremely

Inverse, Fixed Time

Time Multiplier:

11 curves for each characteristic

Timing Accuracy:

±

1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap

and is for a given measured multiple of tap.

Setting Range:

0.1 to 9.9 s

Fixed Timing

Setting Increment:

0.1 s

Timing Accuracy:

±

1 cycle, ±2% of the time to trip for time dial settings ≥ 0.1.

Integrating:

Simulates the disk reset of electromechanical relays and begins when

the current decreases below 95% of pickup. Appendix A, Characteristic

Curves illustrates the integrating reset characteristic curve and equation.

Reset

Instantaneous:

Reset occurs within 16 ms of when the current decreases below 95% of

the pickup level.

Instantaneous Overcurrent A (50-A) Element

Setting Range:

2 to 99 Aac

BE1-50/51B-244 Pickup

Setting increment:

1 Aac

Accuracy:

Sum of ±2% and ±25 mAac

Dropout occurs at 95% of pickup value.

Dropout