1-4

BE1-50/51B-244 General Information

9252000793 Rev C

Figure 1-2. Current Sensing Input Burden (BE1-50/51B-244)

Frequency Response

A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for

pickup.

Transient Response

<10% overreach with system time constants up to 40 ms.

Harmonic Rejection

Rejection of odd and even harmonics is illustrated in Figure 1-3.

Figure 1-3. Harmonic Rejection