BE1-50/51B-244 General Information

1-3

Switch selectable—no intentional delay (SW3-2 OFF) or a fixed delay of 100 ms (SW3-2 ON). Appendix

A, Characteristic Curves illustrates the characteristic curve for the 50-A and 50-B elements.

Time Delay

Instantaneous Overcurrent B (50-B) Element

Setting Range:

1 to 15.9 Aac

BE1-50/51B-244 Pickup

Setting increment:

0.1 Aac

Accuracy:

Sum of ±2% and ±25 mAac

Dropout occurs at 95% of pickup value.

Dropout

Fixed at no intentional delay. Appendix A, Characteristic Curves illustrates the characteristic curve for the

50-A and 50-B elements.

Time Delay

Resets within 16 ms of when sensed current decreases below the pickup level.

Reset Characteristic

Current Sensing Input

Continuous Rating:

14 Aac ∗

BE1-50/51B-244

1 Second Rating:

400 Aac

Continuous rating is 14 Aac for temperatures up to 45°C. See Figure 1-1 for derating curve.

Figure 1-1. Current Sensing Input Derating Curve (BE1-50/51B-244)

Figure 1-2

BE1-50/51B-244 Burden

illustrates the current sensing input burden characteristic.

At 0.5 Aac:

2.8 Ω

At 5.0 Aac:

0.3 Ω