Factory settings, Factory settings -2, Figure 4-2. outline dimensions, ft11 case – Basler Electric BE1-50/51B-244 User Manual
Page 30: Figure 4-3. outline dimensions, ft21 case
Advertising
4-2
BE1-50/51B-244 Installation
9252000793 Rev C
Figure 4-2. Outline Dimensions, FT11 Case
Figure 4-3. Outline Dimensions, FT21 Case
Factory Settings
Factory settings for the internal switches of SW3 and jumper settings are as follows:
•
SW3-1 — OFF (60 hertz operation).
•
SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element).
•
SW3-3 — OFF (Westinghouse CO type characteristic curves).
•
SW3-4 — ON (Integrating reset characteristics).
•
J1 pins 2-3 — 50-A minimum target operating current of 80 to 200 mA
•
J2 pins 2-3 — 51 minimum target operating current of 80 to 200 mA