4-2

BE1-50/51B-244 Installation

9252000793 Rev C

Figure 4-2. Outline Dimensions, FT11 Case

Figure 4-3. Outline Dimensions, FT21 Case

Factory Settings

Factory settings for the internal switches of SW3 and jumper settings are as follows:

SW3-1 — OFF (60 hertz operation).

SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element).

SW3-3 — OFF (Westinghouse CO type characteristic curves).

SW3-4 — ON (Integrating reset characteristics).

J1 pins 2-3 — 50-A minimum target operating current of 80 to 200 mA

J2 pins 2-3 — 51 minimum target operating current of 80 to 200 mA